Description of the XCL8010AU Controller Module
Corresponding Terminal Sockets
Table 6. I/O modules and corresponding terminal sockets
I/O module
socket
XF821AU,
XFL821AU
XF822AU,
XS821-22
XFL822AU,
XFLR822AU,
XFR822AU
XF823AU,
XS823
XFL823AU
XF824AU,
XFL824AU,
XFLR824AU,
XS824-25
XFR824AU
XFR825AU

Interfaces and Bus Connections

The Excel 800 System can be connected to the following
devices and systems:
Panel Bus
• For communication with up to 16 Panel Bus I/O modules
• Polarity-insensitive
LonWorks Bus
• For communication with other L
within the building
• FTT10, link power compatible
• Polarity-insensitive
C-Bus
• For communication with other controllers
HMI
• For connecting an operator interface, e.g., XI582 or a
laptop, e.g., for CARE
Modem
• NO CONNECTION
EN1B-0410GE51 R0908A
scope of delivery
1 terminal socket,
1 bridge connector
1 swivel label holder
1 terminal socket,
1 bridge connector
1 swivel label holder
1 terminal socket,
1 bridge connector
1 swivel label holder
1 long cross connector
W
Bus devices
ON
ORKS

Technical Data

System Data

Table 7. System data
Operating voltage
Power consumption

Operational Environment

Table 8. Operational environment
ambient operating
temperature
ambient operating
humidity
ambient storage
temperature
ambient storage
humidity

Smoke Control Configuration

SMOKE CONTROL CONFIGURATION
XL800
UL-LISTED
8
FIRE ALARM
CONTROL UNIT
FIREFIGHTERS'
SMOKE CONTROL
PANEL (FSCS)
14505068
AUDIBLE
ANNUNCIATOR
1
Fig. 8. Typical smoke control configuration
NOTES:
1
Locate and configure per NFPA 92A, Section 3-4.3.4.
UL-listed annunciator / FSCS panel switches have a
minimum rating of 24 V, 1/10 Amp, and lamps / LEDs
have a rating of 24 V, limited to 50 mA.
2
Locate so as to minimize control wiring and piping.
Avoid running wires or piping through areas that have
a high fire risk.
3
Locate per UL 555S.
10
24 VAC/DC, 60 Hz
Max. 3.57 A
(1 XCL8010AU Controller
+ 16 I/O modules)
0 ─ 49 °C (32 ─ 122 °F)
5 ─ 93 % rel. humidity
(non-condensing)
–20 ─ +70 °C (–4 ─ +158 °F)
5 ─ 95 % rel. humidity
(non-condensing)
9
AO
SUPPLY
FAN
11
AIRFLOW SENSOR
AO
EXHAUST
FAN
12
AO
2
DAMPER
VERIFICATION
6
STATUS CONTROL
10
Excel 800
4
5
3
7