IDC Installation Plan and Unpacking

2.2.1 Environmental Considerations

The life of the IDC is adversely affected if the installation does not meet the following
guidelines:
The system must be installed on a level floor suitable for computer or electronic
equipment.
The system must be installed in a temperature and humidity controlled indoor area free
of conductive contaminants.
Failure to follow guidelines may void your warranty.

2.2.2 Preparing for Wiring the IDC

NOTE
with two upstream feeder breakers, must be provided. One for the UPS and one for the
IDC bypass input. DO NOT use one feed or a single feeder breaker to supply both the
UPS and IDC.
Power and control wiring for a line-up-and-match IDC are supplied with the cabinet.
Wiring requirements for an IDC installed separate from the UPS cabinet, including the
minimum AWG size of external wiring, can be found on Drawing 164201560-5 starting on
page A-10. The input power wiring connections for this equipment are rated at 90°C. If
wire is run in an ambient temperature greater than 40°C, higher temperature wire and/or
larger size wire may be
Drawing 164201560-8 starting on page A-23 and should be connected at the IDC interface
terminal block located inside the IDC.

2.3 Inspecting and Unpacking the IDC

The cabinet is shipped bolted to a wooden pallet (see Figure 2-1) and protected with outer
protective packaging material.
The IDC is heavy (see Table A on page A-4). If unpacking instructions are not closely followed,
the cabinet may tip and cause serious injury.
1. Carefully inspect the outer packaging for evidence of damage during transit.
Do not install a damaged cabinet. Report any damage to the carrier and contact your Eaton
service representative immediately.
2. Use a forklift or pallet jack to move the packaged cabinet to the installation site,
2-2
EATON Powerware
A minimum of two separate feeds with upstream feeder breakers, or one feed
necessary.
or as close as possible, before unpacking. Insert the forklift or pallet jack's forks
between the pallet supports on the bottom of the unit.
9390 IDC Installation and Operation Manual S 164201560 Rev C www.powerware.com
®