Active Trouble Monitor Mode of Operation

3.10.2 How the Control Panel Indicates an Active Fire Control
Activation of a
Initiate the monitor module Control-by-Event
Send a message to the LCD display, History buffer and installed printers, FDU-80
annunciators, and CRT-2s
Display an
information specific to the device
3.10.3 How the Control Panel Indicates an Active Non-Fire Point
Non-Fire point operation does not affect control panel operation, nor does it display a message at
the panel LCD. Activation of a Non-Fire point activates CBE—but does not cause any indication
on the control panel. For example, you can program a Non-Fire point to turn lights in a zone to a
lower setting when activated. In this case, when the point activates the control panel activates the
point's CBE to turn the lights down without any audio or visual indication on the control panel.

3.11 Active Trouble Monitor Mode of Operation

3.11.1 How the Control Panel Indicates an Active Trouble Monitor
Trouble Monitor Points are monitor modules programmed with the following Type Codes:
Type Code
EQUIP MONITR
POWER MONITR
TROUBLE MON
These types of monitor modules operate like monitored system functions that can produce
troubles—but with the following differences:
The LCD display status banner displays
Extended 12 character
custom label
The monitor module is non-latching: the module will return to normal when the trouble
condition no longer exists.
The monitor modules activate Control-by-Event
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
point causes the control panel to do the following:
FIRE CONTROL
status banner and
ACTIVE
FIRE CONTROL
Status banner
Type Code
A C T I V E F I R E C O N T R O L I N T E N S I V E C A R E U N I T
E A S T E R N W I N G
Z 0 5 5
Figure 3.13 Sample Fire Control Point Display
Latching
(Y/N)
N
Used for recording access to monitored equipment Activates CBE
N
Used to monitor remote power supplies or other
external equipment
N
Used to monitor remote power supplies or other
external equipment
Table 3.6 Trouble Monitor Type Codes
Status banner
T R O U B L T R O U B L E _ M O N
E A S T E R N W I N G
Figure 4 Sample Trouble Monitor Point Message
Operation of the Control Panel
Type Code on the LCD display, along with
0 8 : 5 9 a 0 1 1 5 1 1 1 M 0 4 4
Zone affected by the Fire Control
Device Function
as shown:
ACTIVE
Type Code
I N T E N S I V E C A R E U N I T
0 9 : 3 8 A 0 1 1 5 1 1 1 M 0 4 4
Time and date of trouble
Point Function
Indicates trouble
Indicates trouble
Custom descriptor for
this device location
Device address