Read Status Operation
Device Status The status of the module: control/relay module [On (device active) OFF (device
not active] or monitor module (Normal, Alarm, or Test).
Type Code The software Type Code that identifies the type of module. (Refer to "Point
Programming" in the NFS-320 Programming Manual.)
CBE list Only the first zone in the device's CBE list will be displayed.
Device SLC Address The SLC address of the module.
Switch Inhibit (control/relay module only) Displays whether the remote ON/OFF capability
of the device is inhibited. (I=on; *=off).
Silenceable (control/relay module only) A selection that specifies if the device can be
silenced during an alarm by pressing the signal silence key. Possible values are: 
* = output nonsilenceable
F = silenceable, resound by fire alarm
U = silenceable, resound by supervisory alarm
B = silenceable, resound by security alarm
T = silenceable, resound by trouble
O = silenceable, does not resound
NOTE: If the "Strobe" Type ID is used with System Sensor Strobe synchronization, F, U, B, T, or
O will silence the entire circuit, "*" will silence the horn portion only.
Walk Test (control/relay module only) A selection that specifies if the device will activate
during a Walk Test.
How to View Read Status for a NAC
Device address
The display and descriptions of the fields are shown below:
Device status
Default zone selection
Device Status The status of the device: ON (device active) OFF (device not active).
Type Code The software Type Code that identifies the type of NAC. Refer to "Appendix F -
Type Codes" in the NFS-320 Programming Manual.
CBE List Only the first zone in the NAC's CBE list will be displayed here.
Device Address The address of the NAC (01-04)
Switch Inhibit A selection for disabling the switch function for the control/relay or
transponder output circuit. (I=on; *=off).
38
next device
previous device
Type Code (CONTROL)
O F F
C O N T R O L
Switch Inhibit: I selected, * not selected
Silenceable: O = selected, * = not selected (default)
Figure 4.3 Sample NAC Read Status Display
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
From the "Read Status" screen, press 0, then press the
key. You can now view Read Status for a NAC as follows:
press
, enter the device address, then press the
OUTPUT
key. For example, to read the status of NAC 0-2: press
, enter 02, then press the
OUTPUT
panel now displays information for a NAC as shown in
Figure 4.3.
Label for the NAC
F R O N T H A L L W A Y N O . 2
Z 0 0 0
* O W
Viewing and Printing a Read Status
ENTER
ENTER
key. The control
ENTER
B 0 2
Address (01-04)
B = NAC
Walk Test selection:
W selected for Walk Test
* not selected