Troubleshooting
4.21 Radiation Fin Temperature Rise
L4
Remote
Controller
Display
Method of
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
Malfunction
compressor on.
Detection
The radiation fin temperature with the compressor on is above 221°F(105°C).
Malfunction
The error is cleared when the temperature drops below 206.6°F(97°C).
Decision
If a radiation fin temperature rise takes place 4 times successively, the system will be shut
Conditions
The error counter will reset itself if this or any other error does not occur during the following 60-
Fin temperature rise due to defective outdoor unit fan
Supposed
Fin temperature rise due to short-circuit
Causes
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Silicon grease is not applied properly on the heat radiation fin after replacing outdoor unit PCB
Foreign matter stuck in the outdoor unit fan
98
down.
minute compressor running time (total time).
SiUS04-924
Service Diagnosis