Thermostat Control
Thermostat control is based on the difference between the room temperature and the set point.
Thermostat OFF Condition
The temperature difference is in zone A.
Thermostat ON Condition
The temperature difference is above zone C after being in zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in zone B.
Cooling / Dry
Heating
18
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
–2.7˚F(–1.5˚C)
2.7˚F(1.5˚C)
ON
C
B
A
OFF
OFF
A
B
C
ON
Room temperature – set point
Cooling : –0.9˚F(–0.5˚C)
Dry : –0.9˚F(–0.5˚C)
Cooling : –3.6˚F(–2.0˚C)
Dry : –4.5~–3.6˚F(–2.5~–2.0˚C)
(R9857)
Room temperature – set point
3.6˚F(2.0˚C)
0.9˚F(0.5˚C)
(R9858)
Function and Control
Main Functions