SiUS04-924
4.18 CT or Related Abnormality
H8
Remote
Controller
Display
Method of
A CT or related error is detected by checking the compressor running frequency and CT-detected
Malfunction
input current.
Detection
Malfunction
The compressor running frequency is below 32 Hz.
Decision
(The input current is also below 0.5 A.)
If this error repeats 4 times, the system will be shut down.
Conditions
The error counter will reset itself if this or any other error does not occur during the following 60-
Power transistor defective
Supposed
Internal wiring broken or in poor contact
Causes
Reactor defective
Outdoor unit PCB defective
Service Diagnosis
minute compressor running time (total time).
Troubleshooting
93