Daikin H-Series Engineering Data

Daikin H-Series Engineering Data

H-series cooling only / heat pump split-system room air conditioners
Hide thumbs Also See for H-Series:

Advertisement

EDUS04-924A
- Cooling Only / Heat Pump -
H-Series

Advertisement

Table of Contents
loading

Summary of Contents for Daikin H-Series

  • Page 1 EDUS04-924A - Cooling Only / Heat Pump - H-Series...
  • Page 2: Table Of Contents

    12.Operation Manual Safety Considerations ..........46 13.Optional Accessories ................82 13.1 Option List ....................82 13.2 <BRC944B2> Wired Remote Controller............. 83 13.3 <KRP413AB1S> Wiring Adaptor for Timer Clock / Remote Controller ..97 13.4 <KRP928BB2S> Interface Adaptor for DIII-NET (Residential Air Conditioner) Room Air Conditioners H-Series...
  • Page 3 EDUS04-924A 13.5 <KPW5E112> Air Direction Adjustment Grille.......... 104 13.6 <KKPR945A4> Drain Plug ............... 105 Room Air Conditioners H-Series...
  • Page 4: Single Split Duct-Free System

    1. Power Supply Indoor Unit Outdoor Unit Power Supply FTXS30HVJU RKS30HVJU FTXS36HVJU RKS36HVJU Single Split  , 208 - 230 V, 60 Hz Duct-Free System FTXS30HVJU RXS30HVJU FTXS36HVJU RXS36HVJU Note: Power Supply Intake ; Outdoor Unit Room Air Conditioners H-Series...
  • Page 5: Functions

    — —   ECONO Operation   Indoor Unit ON/OFF Button   Signal Receiving Sign   R/C with Back Light Temperature Display — —  : Holding Functions Note: — : No Functions Room Air Conditioners H-Series...
  • Page 6: Specifications

    The data are based on the conditions shown in the table below. Cooling Piping Length Conversion Formulae Indoor :80°FDB(27°CDB), 67°FWB(19.4°CWB), kcal/h = kW × 860 / Btu/h = kW × 3412 cfm 25 ft (7.5 m) Outdoor ; 95°FDB( 35°CDB) / 75°FWB( 24°CWB) = m³/min × 35.3 Room Air Conditioners H-Series...
  • Page 7: Heat Pump - 60 Hz, 208 - 230 V

    Indoor ; 70°FDB(21°CDB),60°FWB(15.5°CWB) kcal/h = kW × 860 / Btu/h = kW × 3412 25 ft (7.5 m) Outdoor ; 95°FDB( 35°CDB) / 75°FWB( 24°CWB) Outdoor ; 47°FDB, 43°FWB (8.3°CDB, 6°CWB) cfm = m³/min × 35.3 Room Air Conditioners H-Series...
  • Page 8: Dimensions

    7-1/2 TERMINAL STRIP NAME PLATE GAS STOP VALVE OUTDOOR AIR LIQUID STOP VALVE THERMISTOR GROUND TERMINAL GAS PIPE (φ5/8 SINGLE UNION) INTERCONNECTING PIPING 3-1/16 3-5/16 1-11/16 LIQUID PIPE AND WIRING INLET 3-1/2 (φ3/8 SINGLE UNION) 3D063154A Room Air Conditioners H-Series...
  • Page 9: Wiring Diagrams

    : PILOT LAMP : POWER MODULE AC1, AC2 PCB1, 2 : PRINTED CIRCUIT BOARD U, V, W, X11A, X12A : REVERSING SOLENOID VALVE COIL E, E2 SHEET METAL : TERMINAL STRIP FIXED PLATE HR1, HR2 : CONNECTOR 3D062017B Room Air Conditioners H-Series...
  • Page 10: Piping Diagrams

    6. Piping Diagrams Indoor Unit FTXS30/36HVJU INDOOR UNIT 5/16 CuT DISTRIBUTOR HEAT EXCHANGER THERMISTOR CROSS FLOW FAN ON HEAT EXCH. FIELD PIPING 3/8 CuT FAN MOTOR HEADER FIELD PIPING 5/8 CuT 1/2 CuT REFRIGERANT FLOW COOLING HEATING 4D062742 Room Air Conditioners H-Series...
  • Page 11: Outdoor Unit

    ON:HEATING 5/8CuT 5/8CuT FUSIBLE PLUG 3/8CuT MUFFLER FIELD PIPING 1/4CuT 3/8CuT LIQUID (3/8 CuT) DISCHARGE PIPE 5/8CuT THERMISTOR GAS LINE STOP VALVE REFRIGERANT FLOW FIELD PIPING COMPRESSOR ACCUMULATOR ACCUMULATOR COOLING HEATING 5/8CuT GAS (5/8 CuT) 3D063153 Room Air Conditioners H-Series...
  • Page 12: Capacity Tables

    INDOOR OUTDOOR –15 (°CDB) °C °C 14.0 20.0 5.49 4.28 0.49 Temp: Fahrenheit TC, SHC: kBtu/h PI: kW 60 Hz, 208 - 230 V INDOOR OUTDOOR 5 (°FDB) °F °F 57.2 68.0 18.73 14.59 0.49 3D071130 Room Air Conditioners H-Series...
  • Page 13 INDOOR OUTDOOR –15 (°CDB) °C °C 14.0 20.0 5.67 4.42 0.54 Temp: Fahrenheit TC, SHC: kBtu/h PI: kW 60 Hz, 208 - 230 V INDOOR OUTDOOR 5 (°FDB) °F °F 57.2 68.0 19.35 15.08 0.54 3D071131 Room Air Conditioners H-Series...
  • Page 14: Heat Pump

    19.21 2.81 21.42 2.89 29.13 3.78 31.83 3.49 31.83 3.01 77.0 14.53 2.65 19.01 2.82 21.21 2.91 28.89 3.80 30.67 3.30 30.67 2.86 80.6 14.12 2.68 18.60 2.85 20.80 2.94 28.36 3.82 28.36 2.94 28.36 2.56 Room Air Conditioners H-Series...
  • Page 15 INDOOR OUTDOOR –15 (°CDB) °C °C 14.0 20.0 5.49 4.28 0.49 Temp: Fahrenheit TC, SHC: kBtu/h PI: kW 60 Hz, 208 - 230 V INDOOR OUTDOOR 5 (°FDB) °F °F 57.2 68.0 18.73 14.59 0.49 3D063318 Room Air Conditioners H-Series...
  • Page 16 18.61 2.69 22.05 2.82 29.98 3.68 34.84 3.87 38.07 3.99 77.0 14.96 2.58 18.40 2.71 21.84 2.83 29.73 3.70 34.59 3.89 37.44 3.92 80.6 14.54 2.61 17.98 2.74 21.42 2.86 29.24 3.73 34.09 3.92 34.62 3.45 Room Air Conditioners H-Series...
  • Page 17 19.67 2.98 23.31 3.12 31.70 4.07 36.83 4.28 38.86 4.08 77.0 15.81 2.85 19.45 2.99 23.08 3.13 31.43 4.09 36.57 4.29 37.44 3.83 80.6 15.37 2.88 19.00 3.02 22.64 3.16 30.91 4.12 34.62 3.96 34.62 3.37 Room Air Conditioners H-Series...
  • Page 18 INDOOR OUTDOOR –15 (°CDB) °C °C 14.0 20.0 5.67 4.42 0.54 Temp: Fahrenheit TC, SHC: kBtu/h PI: kW 60 Hz, 208 - 230 V INDOOR OUTDOOR 5 (°FDB) °F °F 57.2 68.0 19.35 15.08 0.54 3D063319 Room Air Conditioners H-Series...
  • Page 19: Capacity Correction Factor By The Length Of Refrigerant Piping (Reference)

    <--- line : heating capacity> R-410A (30/36 class) Range of the Refrigerant Additional Charge 16.4 32.8 49.2 65.6 82.0 98.4 Piping length (ft) (R4981) Note: The graph shows the factor when additional refrigerant of the proper quantity is charged. Room Air Conditioners H-Series...
  • Page 20: Operation Limit

    · Equivalent piping length 25ft · Level difference 3D063168 · Air flow rate High NOTE: Operation can be extended to 0°F in cooling & heating with use of the optional wind baffle. Room Air Conditioners H-Series...
  • Page 21: Sound Level

    2. The data are based on the conditions shown in the table below. Cooling Heating Piping Length Indoor ; 80°FDB / 67°FWB Indoor ; 70°FDB / 60°FWB 16.4 ft Outdoor ; 95°FDB / 75°FWB Outdoor ; 47°FDB / 43°FWB Room Air Conditioners H-Series...
  • Page 22: Octave Band Level

    60Hz 208/230V (L) Cooling Heating NC-20 NC-20 APPROXIMATE APPROXIMATE THRESHOLD HEARING THRESHOLD HEARING FOR CONTINUOUS FOR CONTINUOUS NOISE NOISE 1000 2000 4000 8000 3D062992 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) Room Air Conditioners H-Series...
  • Page 23 Cooling NC-30 NC-30 NC-20 NC-20 APPROXIMATE APPROXIMATE THRESHOLD HEARING THRESHOLD HEARING FOR CONTINUOUS FOR CONTINUOUS NOISE NOISE 1000 2000 4000 8000 1000 2000 4000 8000 3D063288 OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) Room Air Conditioners H-Series...
  • Page 24: Electric Characteristics

    3. Select wire size based on the larger value of MCA. : Rated load amps (A) : Outdoor fan motor : Indoor fan motor : Fan motor rated output (W) : Full load amps (A) 3D063167 3D071271 Room Air Conditioners H-Series...
  • Page 25: Installation Manual

    • Do not change the setting of the protection devices. If • Only qualified personnel must carry out the installation the pressure switch, thermal switch, or other work. Installation must be done in accordance with this protection device is shorted and operated forcibly, or Room Air Conditioners H-Series...
  • Page 26 EDUS04-924A Installation Manual parts other than those specified by Daikin are used, operation is not possible when connected to other fire or explosion may occur. units. • Do not touch the switch with wet fingers. Touching a • Remote controller (wireless kit) transmitting distance switch with wet fingers can cause electric shock.
  • Page 27: Choosing An Installation Site

    For heat pump (Outdoor unit model: RXS) • Check that the DIP switch are on the heat pump side. DIP switch If they are set on the cooling only side, move them to the heat pump side. Heat pump Cooling only Room Air Conditioners H-Series...
  • Page 28: Indoor Unit Installation Drawings

    1) Do not hit or forcefully push the intelligent- eye sensor . . This can lead to damage and malfunction. 2) Do not place large objects near the sensor. Keep heating units or humidifiers outside the sensor’s detection area. Room Air Conditioners H-Series...
  • Page 29: Installation Tips

    2) Insert a wall pipe into the hole. (Field supply) Wall embedded 3) Insert a wall cover into wall pipe. pipe (Field supply) 4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole gap with putty. Room Air Conditioners H-Series...
  • Page 30: Indoor Unit Installation

    Left-side, left-back, or left-bottom piping 1-15/16” Drain hose (50mm) or more 1) Insert the drain hose to this depth so it won’t be pulled out of Vinyl chloride drain pipe Outer wall the drain pipe. (VP-30) Room Air Conditioners H-Series...
  • Page 31 (nominal diameter 1/2 inch (13mm)) as a joint. Drain hose supplied with Commercially available drain Commercially available rigid the indoor unit socket polyvinyl chloride pipe (nominal diameter 1/2 inch (13mm)) (nominal diameter 1/2 inch (13mm)) Room Air Conditioners H-Series...
  • Page 32: Refrigerant Piping Work

    Thickness 0.393 inch (10mm) Min. 1-15/16 inch (50mm) or more 1-3/16 inch (30mm) or more Thickness 0.039 inch (1mm) (C1220T-O) Thickness 0.031 inch (0.8mm) (C1220T-O) 3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes. Room Air Conditioners H-Series...
  • Page 33: Pump Down Operation

    • If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation mode when the circuit breaker is opened again. Room Air Conditioners H-Series...
  • Page 34 Stop valves are opened. Indoor unit properly receives remote controller Inoperative commands. The heat pump or cooling only mode is selectable Remote controller malfunctioning with the DIP switch of the remote controller. 3P228446-6G Room Air Conditioners H-Series...
  • Page 35: Outdoor Unit

    Daikin are used, • Only qualified personnel must carry out the installation fire or explosion may occur.
  • Page 36 Normal operation is not possible when connected to other units. • Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types). Room Air Conditioners H-Series...
  • Page 37: Precautions On Installation

    1/2 inch (M12) foundation bolts, nuts and washers each which are available on the market.) • It is best to screw in the foundation bolts until their length are 3/4 inch (20mm) from the foundation surface. Room Air Conditioners H-Series...
  • Page 38: Installation Guidelines

    More than 3-15/16” More More than (100mm) than 47-1/4” 13-3/4” More than 13-3/4” 3-15/16” (1200mm) More than 1-15/16” (350mm) (350mm) (100mm) or less (50mm) More than 1-15/16” Top view More than 1-15/16” Top view (50mm) (50mm) Side view Room Air Conditioners H-Series...
  • Page 39: Outdoor Unit Installation

    If the drain holes of the outdoor unit are covered with the mounting bracket or the floor, raise the unit to provide the space of more than 3-15/16 inch (100mm) under the leg of the outdoor unit. Room Air Conditioners H-Series...
  • Page 40 5/8 inch(15.9mm) 3/8 inch(9.5mm) Do not apply refrigeration oil to the flare nut avoid • • 35.5-44.0ft 15.9-20.2ft tightening with over torque. • • (48.1-59.7N (21.6-27.4N Service port cap tightening torque • • 7.9-10.8ft lbf (10.8-14.7N Room Air Conditioners H-Series...
  • Page 41 *2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4). Room Air Conditioners H-Series...
  • Page 42 Gas stop valve Liquid stop valve Forced cooling operation valve cap 1) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again to stop forced cooling. S102 LED-A Forced operation switch Room Air Conditioners H-Series...
  • Page 43 6) Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire. <Method of Mounting Conduit> Pass wires through the conduit and secure them with a lock nut. Lock nut Wire retainer Conduit mounting plate Service port Conduit mounting plate Conduit Room Air Conditioners H-Series...
  • Page 44 Problems with the work may cause heat and fires. Stripping wire at terminal block Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop. Room Air Conditioners H-Series...
  • Page 45 3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. A humidifier might cause dew jumping from the indoor unit outlet vent. 4) Use the indoor unit at the highest level of air flow rate. Room Air Conditioners H-Series...
  • Page 46 The specified wires are used for inter-unit wiring. Inoperative or burn damage Indoor or outdoor unit’s air intake or exhaust has clear path of air. Incomplete cooling/heating function Stop valves are opened. Indoor unit properly receives remote controller Inoperative commands. 3P235796-1F Room Air Conditioners H-Series...
  • Page 47: Operation Manual Safety Considerations

    Inform customers that they should store this Operation leakage, electric shock, and fire. Only use Manual with the Installation Manual for future reference. accessories made by Daikin that are specifically designed for use with the equipment and have them Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols: installed by a professional.
  • Page 48 • Do not attempt to do electrical work or grounding conditioner or heat pump as they can cut and cause work unless you are licensed to do so. Consult with injury. your dealer for electrical work and grounding work. Room Air Conditioners H-Series...
  • Page 49 Stop operating the air conditioner or heat pump and contact your dealer. Room Air Conditioners H-Series...
  • Page 50 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 51 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 52 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 53 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 54 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 55 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 56 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 57 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 58 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 59 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 60 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 61 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 62 EDUS04-924A Operation Manual Safety Considerations Keep heating units or humidifiers outside the sensor’s detection range. Do not hit or focefully push the INTELLIGENT EYE sensor. This can lead to damage and malfunction. Room Air Conditioners H-Series...
  • Page 63 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 64 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 65 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 66 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 67 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 68 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 69 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 70 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 71 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 72 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 73 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 74 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 75 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 76 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 77 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 78 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 79 Operation Manual Safety Considerations EDUS04-924A Room Air Conditioners H-Series...
  • Page 80 EDUS04-924A Operation Manual Safety Considerations Room Air Conditioners H-Series...
  • Page 81 We recommend periodic maintenance by a specialist in addition to regular cleaning by the user. For specialized maintenance, contact the service shop where you purchased the air conditioner. The maintenance cost must be born by the user. Room Air Conditioners H-Series...
  • Page 82 EDUS04-924A Operation Manual Safety Considerations 3P228444-4H Room Air Conditioners H-Series...
  • Page 83: Optional Accessories

    5 Standard accessory BRCW901A08 is necessary. 2 A wiring adaptor (KRP413AB1S) is also required for each indoor unit. 13.1.2 Outdoor Unit Option Name Model Name Air Direction Adjustment Grille KPW5E112  Drain Plug KKP945A4 Note:  Standard accessory Room Air Conditioners H-Series...
  • Page 84: Brc944B2> Wired Remote Controller

    Secure the remote controller lower case with the two supplied machine screws. KJB2121A KJB1111A Switch box (Field supplied parts) Machine screws (M4 × 16) For the field supplied switch box, use optional accessories KJB1111A or KJB2121A. Room Air Conditioners H-Series...
  • Page 85 (Remote controller cord 4 wire) 5. Temperature indication change To change from Celsius temperature indication to Fahrenheit one Press and hold down at the same time for 5 seconds while the Celsius temperature is indicated. ← See Operation Manual 3P202923-2B Room Air Conditioners H-Series...
  • Page 86 Sets the current time and timer. Adjusts the temperature setting. CAUTION •This remote controller cannot be used together with a standard wireless remote controller. Otherwise, what appears on this remote controller's display may fail to correspond to actual operating conditions. Room Air Conditioners H-Series...
  • Page 87: Preparation Before Operation

    Room temp. Less than 80% Indoor humidity two weeks as required) or so. -15 to 20 ˚C (5˚F to 68˚F) Outdoor temp. Heating Less than 27 ˚C Room temp.  Operation limit differ according to the model. Room Air Conditioners H-Series...
  • Page 88 19˚C (66˚F). In this case, no change by the temperature indication change is observed.  When the temperature indication change is set, the preset temperature is transmitted to the indoor unit so that the reception sound will be heard from the indoor unit. Room Air Conditioners H-Series...
  • Page 89 Note  While running in the DRY mode, you may feel cool or warm air from the air outlet. In this case, readjust the airflow direction with the vertical airflow direction louvers. (except Duct Connected type) Room Air Conditioners H-Series...
  • Page 90  Since the air conditioner heats the whole room by circulating hot air, it takes some time to heat the entire room completely. Room Air Conditioners H-Series...
  • Page 91: Adjusting Airflow Direction

    This will enhance the cooling and heating effect.  On the air conditioners with vertical and horizontal swing function, be sure to adjust the airflow directions using the remote controller. Do not forcibly adjust louvers by hand or a malfunction may occur. Room Air Conditioners H-Series...
  • Page 92 This function cannot be used. Note  The operating procedure and remote controller display are different depending on the indoor unit being connected. Read How to Adjust the Airflow Direction in the air conditioner’s Operation Manual. Room Air Conditioners H-Series...
  • Page 93: Timer Operation

     If one minute has passed before making any timer setting, the previous timer settings are reintroduced and the timer is on standby. In this case, use the (time setting) button and make your desired timer settings. Room Air Conditioners H-Series...
  • Page 94  The circuit breaker has been programmed. and system starts. and system stops. The set time is The ON timer setting The timer setting no activated. displayed. no longer displays. longer displays.  The power fails. Room Air Conditioners H-Series...
  • Page 95 Example of display with DAILY timer programmed Note  The system starts and stops repeatedly until the DAILY timer is set off. Before you leave home for a Timers Timer alone long time, set the DAILY timer off. programmed. programmed. Room Air Conditioners H-Series...
  • Page 96: Daily Timer

    The 24-hour timer display The 24-hour timer display is blinking. is blinking. This means that Timers This means that the timer has not been programmed for the same time settings. programmed yet. New time settings must be made. Room Air Conditioners H-Series...
  • Page 97 The airflow rate remains the same, and is not adjustable. Run the system when the room temperature is below 28°C (82°F). Finally turn off the circuit breaker dedicated for the room air conditioner. Clean the air filter and place it back into position. 3P202922-2B Room Air Conditioners H-Series...
  • Page 98: Krp413Ab1S> Wiring Adaptor For Timer Clock / Remote Controller

    EDUS04-924A Optional Accessories 13.3 <KRP413AB1S> Wiring Adaptor for Timer Clock / Remote Controller ground line. Room Air Conditioners H-Series...
  • Page 99 Optional Accessories EDUS04-924A appropriate tool, such as wire cutters. Room Air Conditioners H-Series...
  • Page 100 EDUS04-924A Optional Accessories Room Air Conditioners H-Series...
  • Page 101 Optional Accessories EDUS04-924A 3P248024-2 Room Air Conditioners H-Series...
  • Page 102: Krp928Bb2S> Interface Adaptor For Diii-Net (Residential Air Conditioner)

    EDUS04-924A Optional Accessories 13.4 <KRP928BB2S> Interface Adaptor for DIII-NET (Residential Air Conditioner) A ground leakage circuit breaker should be installed. Room Air Conditioners H-Series...
  • Page 103 Optional Accessories EDUS04-924A kit’s case 4” (100 mm) 3P248024-1A Room Air Conditioners H-Series...
  • Page 104 HA casing along the frame. Then cut the part with an appropriate tool, such as a pair of wire cutters. NOTE: Cut off only the thin part required for wiring. Room Air Conditioners H-Series...
  • Page 105: Before Installation

    Faces onto the street where pedestrians are directly exposed to the exhaust. Garden trees are directly exposed to the exhaust. Required Installation Space A minimum clearance of 4” (100mm) is required between the back of the outdoor unit and obstacles (such as walls). Room Air Conditioners H-Series...
  • Page 106 EDUS04-924A Optional Accessories 13.6 <KKPR945A4> Drain Plug 4"/ Room Air Conditioners H-Series...
  • Page 107 In the lower direction Standard grille Standard grille In the left direction In the right direction Standard grille Standard grille Illustration showing the completion of the air direction adjustment grille mounted (with the air blowing in the upper direction) Room Air Conditioners H-Series...
  • Page 108 Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms tot he applicable standards, and is suitable for use, in the region where the product will be used.

Table of Contents