Troubleshooting
4.9
OL Activation (Compressor Overload)
E5
Remote
Controller
Display
Method of
A compressor overload is detected through compressor OL.
Malfunction
Detection
If the compressor OL is activated twice, the system will be shut down.
Malfunction
The error counter will reset itself if this or any other error does not occur during the following 60-
Decision
Conditions
The operating temperature condition is not specified.
Refrigerant shortage
Supposed
Four-way valve malfunctioning
Causes
Outdoor unit PCB defective
Water mixed in the local piping
Electronic expansion valve defective
Stop valve defective
Troubleshooting
Check No.04
Refer to P.106
Check No.05
Refer to P.107
Check No.06
Refer to P.108
Check No.11
Refer to P.110
82
minute compressor running time (total time).
Be sure to turn off the power switch before connecting or disconnecting
Caution
the connector, or parts damage may occur.
Discharge pipe
thermistor disconnected?
NO
Check No. 06
Check the thermistors.
Functioning
Check No. 04
Check the electronic
expansion valve.
Functioning
Check No. 05
Check the four-way valve.
Functioning
Check No. 11
Check the refrigerant line.
Functioning
YES
Malfunctioning
* Discharge pipe thermistor
Malfunctioning
Malfunctioning
Malfunctioning
* Refrigerant shortage
* Water mixed
* Stop valve defective
SiUS04-924
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the valve itself or
the coil.
Replace the four-way valve
coil or the valve itself.
Replace the outdoor unit
PCB.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R7137)
Service Diagnosis