SiUS04-924
4.17 Position Sensor Abnormality
H6
Remote
Controller
Display
Method of
A compressor startup failure is detected by checking the compressor running condition through the
Malfunction
position detection circuit.
Detection
The compressor fails to start in about 15 seconds after the compressor run command signal is
Malfunction
Decision
Clearing condition: Continuous run for about 5 minutes.
Conditions
The system will be shut down if the error occurs 8 times.
Compressor relay cable disconnected
Supposed
Compressor itself defective
Causes
Outdoor unit PCB defective
Stop valve closed
Input voltage out of specification
Service Diagnosis
sent.
Troubleshooting
91