Fan Speed Control For Indoor Units - Daikin FTXS30HVJU Service Manual

Inverter pair wall mounted type h-series
Hide thumbs Also See for FTXS30HVJU:
Table of Contents

Advertisement

Main Functions
1.3

Fan Speed Control for Indoor Units

Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and Hall IC control.
For more information about Hall IC, refer to the troubleshooting section, Fan Motor (DC Motor) or
Related Abnormality on page 76.
Phase Steps
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
In automatic fan speed operation, the step "SL" is not available.
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
Note:
1. During POWERFUL operation, fan operates H tap + 50 rpm.
2. Fan stops during defrost operation.
3. With the thermostat OFF, the fan rotates at the following speed.
Automatic
In heating mode, the indoor fan speed will be regulated according to the indoor heat exchanger
Airflow Control
temperature and the difference between the room temperature and the required set point.
for Heating
Automatic
The following drawing explains the principle of fan speed control for cooling:
Airflow Control
for Cooling
Note:
*: In automatic fan speed operation, upper limit is at M tap within 30 minutes from the operation
start.
 The airflow rate is controlled automatically within the following steps.
COMFORT
AIRFLOW Mode
 The latest command has the priority between POWERFUL and COMFORT AIRFLOW.
Function and Control
Step
= The airflow rate is automatically controlled within this range when the FAN setting button
is set to automatic.
Cooling: The fan keeps rotating at the set tap.
Heating: The fan stops.
Dry: The fan stops after rotating for a few minutes at LL tap.
fan speed
+4.5˚F(+2.5˚C)
+2.7˚F(+1.5˚C)
+0.9˚F(+0.5˚C)
Thermostat
setting
temperature
Cooling: L tap – MH tap (same as AUTOMATIC)
Heating: L tap – M tap
Cooling
(R6833)
MH*
+5.4˚F(+3˚C)
M
+3.6˚F(+2˚C)
ML
+1.8˚F(+1˚C)
L
Phase control
SiUS04-924
Heating
(R6834)
Difference between room
and set temperature
(R9854)
15