Current consumption:
• 250 mA max. (5 V), supplied by the RMIO board
• 15 mA max. (24 V) from the network supply.
General:
• Estimated min. lifetime: 100 000 h
• All materials are UL/CSA approved
• Complies with EMC Standards EN 50081-2 and EN 50082-2

Fieldbus link

Compatible Devices: Any ODVA-compliant DeviceNet scanner
supporting Poll - Response commands to Group 2 only Slaves
Medium:
• Termination: 121 ohm, 1%, Metal Film, 1/4 W
• DeviceNet Cables:
YR-29790 (Thick DeviceNet Cable)
YR-29832 (Thin DeviceNet Cable)
• Maximum Bus Length: 1200 m
Topology: Multi-drop
Serial Communication Type: Asynchronous, half Duplex
Transfer Rate: 125, 250 or 500 kbit/s
Protocol: DeviceNet
Technical data