Installation problems

Verify all the connections on the module:
• Check that the DeviceNet cables are connected to terminal
block X1 as described in chapter
• Check that an external voltage of 24 V DC is applied to
terminals X1:1 and X1:5.
• Check that the RDNA-01 module is properly inserted into the
option slot.
• Check the fastening of the RDNA-01 module with the 2 screws.

Drive setup

The fieldbus parameter group is not shown on the panel:
• Enable the RDNA-01 by setting the appropriate drive
parameter.
The RDNA-01 is using default values:
• Verify that the fieldbus parameter group is set up correctly. If so,
turn off and on the power to the drive or issue a 'Fieldbus
Adapter parameter refresh' command. This will make the
module re-read its setup parameters.
Drive actual values can be read, but the control commands (start/
stop or reference) do not go through:
• Check that the control location parameters of the drive are set to
use the RDNA-01 as the source of the required command.
• Check that the drive is in REMOTE control.

PLC programming

The PLC program is beyond ABB Drives support. Contact the
manufacturer for assistance.

Scanner fault indications

Refer to scanner documentation.