24
Note: The new settings take effect only when the module is
powered up the next time or when a 'Fieldbus Adapter parameter
refresh' is given (see the drive documentation).

Example Configurations

ODVA Basic Speed Control on ACS800
Drive Parameter
10.01 EXT1 STRT/STP/DIR
10.03 REF DIRECTION
11.03 EXT REF1 SELECT
16.01 RUN ENABLE
16.04 FAULT RESET SEL
51.01 MODULE TYPE
51.02 Module MacID
51.03 Module baud rate
51.04 HW/SW option
51.05 Stop function
51.06 Output instance
51.07 Input instance
98.02 COMM MODULE LINK
98.07 COMM PROFILE
Quick start-up guide
Example setting for ACS800
COMM.CW
REQUEST
COMM. REF
YES
COMM.CW
DEVICENET (Verify only)
2
2 (500 kbit/s)
1 (use software settings)
0 (ramp stop)
20 (ODVA Basic Speed Control)
70 (ODVA Basic Speed Control)
FIELDBUS
GENERIC