Quick start-up guide

Overview

This chapter presents the steps to take during the start-up of the
RDNA-01 DeviceNet Adapter Module. For more detailed
information, see the chapters
installation, and
WARNING! Follow the safety instructions given in this manual and
the Hardware Manual of the drive.

PLC Configuration

This is an example on how to configure an Allen-Bradley
ControlLogix 5555 PLC with a 1756-DNB 1756 DeviceNet
Scanner to use an ACS800 equipped with an RDNA-01 fieldbus
adapter.
• Select and import the EDS file for drive, for example
ACS800_Standard_RDNA01_appl1.36_Typical_filerev3.2.EDS.
For more help on choosing the correct file, refer to ABB EDS
Selection Guide document delivered with the EDS files.
Note: Only one EDS file with the same Product ID and Vendor
code can be installed in the PLC at a time.
Mechanical
Drive configuration
installation,
elsewhere in this manual.
Quick start-up guide
19
Electrical