14.3
Multiple Module Parallel Specifications
Eaton 9390 UPS (100–160 kVA) Installation and Operation Manual
14.3.1
UPM Input
Same as single module.
14.3.2
UPM Output
Same as single module.
14.3.3
Environmental
Same as single module.
14.3.4
Battery
Same as single module.
14.3.5
Module Tie Cabinet Input
Operating Input Voltage
(UPM Dependent)
Operating Input Current
14.3.6
Module Tie Cabinet Output
Operating Output Voltage
(UPM Dependent)
Operating Output Current
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
380 Vac for operation from 323 Vac to 418 Vac
400 Vac for operation from 340 Vac to 440 Vac
415 Vac for operation from 353 Vac to 457 Vac
480 Vac for operation from 408 Vac to 528 Vac
See Appendix A, Table O through Table Q.
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
380 Vac for operation from 323 Vac to 418 Vac
400 Vac for operation from 340 Vac to 440 Vac
415 Vac for operation from 353 Vac to 457 Vac
480 Vac for operation from 408 Vac to 528 Vac
See Appendix A, Table O through Table Q.