Multiple Module Parallel Specifications; Upm Input; Upm Output; Environmental - Eaton Powerware 9390 Installation And Operation Manual

Powerware series 100–160 kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

14.3

Multiple Module Parallel Specifications

Eaton 9390 UPS (100–160 kVA) Installation and Operation Manual
14.3.1

UPM Input

Same as single module.
14.3.2

UPM Output

Same as single module.
14.3.3

Environmental

Same as single module.
14.3.4

Battery

Same as single module.
14.3.5

Module Tie Cabinet Input

Operating Input Voltage
(UPM Dependent)
Operating Input Current
14.3.6

Module Tie Cabinet Output

Operating Output Voltage
(UPM Dependent)
Operating Output Current
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
380 Vac for operation from 323 Vac to 418 Vac
400 Vac for operation from 340 Vac to 440 Vac
415 Vac for operation from 353 Vac to 457 Vac
480 Vac for operation from 408 Vac to 528 Vac
See Appendix A, Table O through Table Q.
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
380 Vac for operation from 323 Vac to 418 Vac
400 Vac for operation from 340 Vac to 440 Vac
415 Vac for operation from 353 Vac to 457 Vac
480 Vac for operation from 408 Vac to 528 Vac
See Appendix A, Table O through Table Q.