Kw Demand Log; Figure 8-13. Kw Demand Log Summary Screen - Eaton Powerware 9390 Installation And Operation Manual

Powerware series 100–160 kva
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

8.2.5

kW Demand Log

Press the METERS pushbutton on the main menu bar to display the Unit Meter
screens. Scroll through the meter screens using the
menu bar until the kW Demand Log Summary screen is displayed.
The kW demand log collects information on events where the unit load exceeds a
user‐defined kW limit within a user‐defined time interval. The user can choose a time
period up to 9999 minutes and a load limit up to 9999 kW. If the limit is exceeded
within a given time period a log event is created. The kW Demand Log Summary
screen displays the number of total times the limit has been exceeded since the last
log reset, the date of the last log reset, the maximum kW reading, and the total time
over the limit. It also displays the average kW over the limit and an estimated number
of kWH used over the limit. Both of these values are calculated using the difference
between the actual measurement reading and the user-defined limit level. For
example, during a 60‐minute interval if the limit is set at 10 kW and the measurement
is a constant 15 kW for the entire period, the average kW over would be 5 kW and the
total kWH used over the limit would be 5 kWH. Figure 8‐13 shows the kW Demand
Log Summary screen.
KW DEMAND LOG SUMMARY
NUMBER OF TIMES OVER LIMIT
LAST LOG RESET
AVERAGE KW OVER LIMIT
MAXIMUM READING (KW)
TOTAL TIME OVER LIMIT
TOTAL KWH USED OVER LIMIT
Eaton 9390 UPS (100–160 kVA) Installation and Operation Manual
LOG
Figure 8‐13. kW Demand Log Summary Screen
or
07/30/2005
*** . ** KW
*** . ** KW
** MINUTES
*** . ** KWH
SETUP
S
164201604 Rev E www.eaton.com/powerquality
USING THE CONTROL PANEL
pushbuttons on the
12
8-11

Advertisement

Table of Contents
loading

Table of Contents