Logic Operations
Operating Procedure
Select the setting for the event input assignment.
When a work bit is selected as event input data, Communications Write
Enable/Disable cannot be assigned to an event input.
12. Changing Control Output and Auxiliary Output Settings
Control output and auxiliary output assignments can be changed. The
items that can be changed depend on the Controller model. For details, re-
fer to 3-5-3 Assigned Output Functions.
In this manual, assigning a work bit to either a control output or an auxiliary
output is considered also assigns the alarms and time signals. For exam-
ple, if work bit 1 is set for the Auxiliary Output 1 Assignment parameter,
then alarms 1 to 3 and time signals are assigned.
13. Displaying Parameter Guides
A description of the parameters can be displayed.
14. Displaying the Work Bit Use Destinations
Display a list of destinations where the work bits are used.
This procedure uses event input 2 to change Auto/Manual status.
Event input 2 ON: Auto
Event input 2 OFF: Manual
Event 2
Reverse
operation
Always OFF
Always OFF
Always OFF
1. Select Logic Operation Editor from the CX-Thermo
tree, and click the Start Button.
2. The Logic Operation Editor will be displayed. Confirm
that the screen for work bit 1 is displayed, and select
Operation 3 from the Operation Type Field.
Work bit 1
Section 4-24
173