Wiring Terminals
Auxiliary Outputs 2, and 3
36
E5AN/EN-HT
Output type
Relay (Position-
proportional mod-
els)
Output Units
Model
Output Type
E53-RN
Relay
E53-QN
Voltage (PNP)
E53-Q3
Voltage (NPN)
E53-Q4
Voltage (PNP)
E53-C3N
4 to 20 mA
E53-C3DN
0 to 20 mA
E53-V34N
0 to 10 V
E53-V35N
0 to 5 V
• The E5CN-HT voltage output (for driving SSR) is not electrically isolated
from the internal circuits. When using a grounding thermocouple, do not
connect any of the control output terminals to the ground. (If a control out-
put terminal is connected to the ground, errors will occur in the measured
temperature as a result of leakage current.) E5AN/EN-HT voltage outputs
(for driving SSR), however, are functionally isolated from the internal cir-
cuits.
• Control output 2 of the E5CN-HT is a voltage output (for driving SSR)
only, and outputs across terminals 11(+) and 12(-), or 14(+) and 15(-).
• Control output 1 (voltage output for driving SSR) and control output 2
(voltage output for driving SSR) are not isolated.
• On the E5CN-HT@2@-500, auxiliary output 1 (SUB1) is output across ter-
minals 7 and 8, and auxiliary output 2 (SUB2) is output across terminals 6
and 8.
• On the E5AN/EN-HT@2@-500, auxiliary output 1 (SUB1) is output across
terminals 9 and 10, auxiliary output 2 (SUB2) is output across terminals 7
and 8.
• On the E5AN/EN-HT@3@-500, auxiliary output 1 (SUB1) is output across
terminals 9 and 10, auxiliary output 2 (SUB2) is output across terminals 7
and 8, and auxiliary output 3 (SUB3) is output across terminals 14, 15
and 16.
• When the Input Error Output parameter is set to ON, the output assigned
to the alarm 1 function turns ON when an input error occurs.
• If the Remote SP Input Error Output parameter is set to ON, the output
assigned to the alarm 1 function will turn ON when an RSP input error
occurs.
• When the HB alarm, HS alarm, or heater overcurrent alarm is used with
the E5CN-HT (with E53-CN@H/HH@N2), alarms are output to the output
assigned to the alarm 1 function.
Specifications
250 VAC 1 A (including inrush current)
Output
method
ON/OFF
250 VAC, 5 A (resistive load), Electrical life:
100,000 operations
ON/OFF
PNP type, 12 VDC, 40 mA (with short-circuit
ON/OFF
protection)
ON/OFF
NPN type, 24 VDC, 20 mA (with short-circuit
protection)
PNP type, 24 VDC, 20 mA (with short-circuit
protection)
Linear
DC 4 to 20 mA, resistive load: 600
Linear
Resolution: Approx. 10,000
DC 0 to 20 mA, resistive load: 600
Resolution: Approx. 10,000
Linear
0 to 10 VDC, resistive load: 1 k
Linear
Resolution: Approx. 10,0000 to 5 VDC,
resistive load: 1 k
Resolution: Approx. 10,000
Section 2-2
Specifications
max.
max.
min.
min.