Program-related Functions

4-15-5 Time signals

Set point
Segment completed.
Wait band
Wait band
Current segment
Timer stopped.
• As soon as the deviation enters the wait band, the program moves to the
next segment.
• The wait operation is not performed if it is disabled by an event input.
• The wait operation is not performed if the wait band is set to OFF.
• A time signal is assigned to an auxiliary output or control output.
• Up to two time signals can be set for each program.
• There are two timers for a time signal: an ON timer and an OFF timer. The
timers start from the beginning of the segment.
• The output turns ON once the ON time has elapsed and turns OFF after
the OFF time has elapsed.
Set point
Time signal output
• The Time Signal 1/2 Set Segment parameters (ts1s) (ts2s) set the seg-
ments in which the time signals will start. The default is 0 (disabled).
• The ON/OFF timing is set using the Time Signal 1/2 ON Time (on1) (on2)
and Time Signal 1/2 OFF Time parameters (of1) (of2). The defaults are
0.00.
• ON Conditions
Next segment
Timer started.
ON time
OFF time
Section 4-15
SP
PV
Time
Time