Moving To The Advanced Function Setting Level; Setting - Omron E5CN-HT User Manual

Digital controllers programmable type
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

Moving to the Advanced Function Setting Level

4-6-2

Setting

Setting the Set Point Upper-limit Value
Operating Procedure
Input Type
in-t
5
Set Point
C
sl-h
Upper-limit
1300.0
C
sl-h
1000.0
Setting the Set Point Lower-limit Value
Operating Procedure
Set Point
C
sl-l
Lower Limit
-200.0
C
sl-l
-100.0
4-7

Moving to the Advanced Function Setting Level

1,2,3...
Set the set point upper and lower limits in the Set Point Upper Limit and Set
Point Lower Limit parameters in the initial setting level. In this example, it is
assumed that the input type is set to a K thermocouple with a temperature
range of 200.0 to 1300.0 C.
200.0
100.0
Set Point Upper Limit = 1000
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Set Point Upper Limit parameter.
3. Use the U and D Keys to set the parameter to 1000.0.
Set Point Lower Limit = 100
1. Select the Set Point Lower Limit parameter in the initial setting level.
2. Use the U and D Keys to set the parameter to 100.0.
Use the following procedure to move to the advanced function setting level.
1. Press the O and M Keys simultaneously for at least three seconds in op-
eration level.
Note The key pressing time can be changed in the Move to Protect Level
Time parameter (advanced function setting level).
Input setting range
Set point limiter
1000.0
Section 4-7
1300.0
111