Test Run; Initializing Parameters - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Test Run

3

Initializing Parameters

• Initialize the parameters using the following procedure.
• To initialize the parameters, set n01 to 8.
Key sequence
Indicator
---
In approximately
1 s.
4
Setting the Motor Current Parameter
• Run the Inverter in V/f control mode for trial operation. The control mode is not initialized. Therefore,
set n002 to 0 for V/f control. Set the motor current parameter in n036 in order to prevent the motor from
burning due to overloading.
H Control Mode Setting
Parame-
Register
ter
n002
0102
Control
mode
selection
4-6
Display
example
Name
Description
Sets the control mode for the
Inverter.
0: V/f control mode
1: Vector control mode
Note
1. The control mode
is not initialized
with n001 set-
tings.
Note
2. There are param-
eters that are
changed accord-
ing to the set
value in n002. For
details, refer to
5-1-2 Setting the
Control Mode
(n002).
Explanation
Power On
Press the Mode Key repeatedly until the PRGM indicator
is lit.
Press the Enter Key. The data of n001 will be displayed.
Use the Increment or Decrement Key to set n01 to 8.
The display will flash.
Press the Enter Key so that the set value will be entered
and the data display will be lit.
Parameter n001 will be initialized and reset to 1 from 8.
The parameter number will be displayed.
Setting
range
0, 1
Chapter 4
Unit of
Default
Chan-
setting
setting
ges dur-
opera-
1
0
No
ing
tion