Basic Operation
H Adjusting Multi-function Analog Input
D Setting the Gain and Bias of Multi-function Analog Voltage/Current Input (n068 to
n072)
• Set the multi-function analog voltage input characteristics in n068 (multi-function analog voltage input
gain) and n069 (multi-function analog voltage input bias). Set the multi-function analog current input
characteristics in n071 (multi-function analog current input gain) and n072 (multi-function analog cur-
rent input bias).
• When the gain is a positive value (>0), the reference value
from the multi-function analog input is calculated by the Inverter as follows:
Reference value = (Analog input (%) + Bias)  ⎟ Gain⎟
• When the gain is a negative value (<0), the reference value from the multi-function analog input is
calculated in the same way as follows:
Reference value = (100 – (Analog input (%) + Bias)  ⎟ Gain⎟
Note 1. The analog input as a percentage is 100% at 10 V or 20 mA.
Note 2. When the reference value is used as the frequency (n004 = 7 or 8, or n077 = 1), the frequency
is calculated as a multiple of the maximum frequency (n011).
Note 3. The calculation method is different from that for the frequency reference input (FR terminal).
Note 4. A negative reference value may result depending on the bias setting, but the minimum refer-
ence value is 0.
n068
Multi-function Analog Voltage
Input Gain
Setting
–255(%) to 255(%)
range
(Max. frequency: 100%)
n069
Multi-function Analog Voltage
Input Bias
Setting
–100(%) to 100(%)
range
(Max. frequency: 100%)
n071
Multi-function Analog Current
Input Gain
Setting
–255(%) to 255(%)
range
(Max. frequency: 100%)
n072
Multi-function Analog Current
Input Bias
Setting
–100(%) to 100(%)
range
(Max. frequency: 100%)
5-16
Register
0144 Hex
Unit of
1%
setting
Register
0145 Hex
Unit of
1%
setting
Register
0147 Hex
Unit of
1%
setting
Register
0148 Hex
Unit of
1%
setting
Chapter 5
Changes during
Yes
operation
Default setting
100
Changes during
Yes
operation
Default setting
0
Changes during
Yes
operation
Default setting
100
Changes during
Yes
operation
Default setting
0