Omron SYSDRIVE 3G3MV SERIES User Manual page 116

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Basic Operation
D Filter Time Constant Settings (n062)
• A primary-delay digital filter can be set for analog frequency references to be input.
• This setting is ideal if the analog input signal changes rapidly or the signal is subject to noise interfer-
ence.
• The larger the set value is, the slower the response speed will be.
n062
Analog Frequency Reference
Filter Time Constant
Setting
0.00 to 2.00 (s)
range
H Multi-function Analog Input
Various auxiliary analog inputs can be set for the Digital Operator's multi-function analog voltage/cur-
rent input. Select from the following functions.
n077
Multi-function Analog Input
Terminal Function Selection
Setting
0 to 4
range
n078
Multi-function Analog Input
Terminal Selection
Setting
0, 1
range
n079
Multi-function Analog Input
Frequency Bias
Setting
0 to 50
range
5-14
Register
013E Hex
Unit of
0.01 s
setting
Register
014D Hex
Unit of
1
setting
Register
014E Hex
Unit of
1
setting
Register
014F Hex
Unit of
1 %
setting
Chapter 5
Changes during
No
operation
Default setting
0.10
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
10