Advanced Operation
and capacity of the motor.) When setting the undertorque detection level, allow for a no-load cur-
rent.
n119
Undertorque detection time
Setting
0.1 to 10.0 (s)
range
Set Values
• Set the undertorque detection time.
• The Inverter will detect undertorque when current (or torque) the same as or lower than the detection
level is output for the preset detection time.
6-34
Register
0177 Hex
Unit of
0.1 s
setting
Chapter 6
Changes during
No
operation
Default setting
0.1 s