Omron SYSDRIVE 3G3MV SERIES User Manual page 202

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Communications
D Response
Normal
Byte No.
1
Slave address
2
Function code (03 Hex)
3
Number of bytes of attached data
4
Data of start register
5
6
Data of next register
7
Data of next register
8
9
:
n–1
CRC-16 check
n
Error
Byte No.
1
Slave address
2
Function code (83 Hex)
3
Error code
CRC-16 check
4
5
Note When an error occurs, the MSB of the function code will be set to 1.
H Example of Data Read
• In the following example, four-register data (status signal data) is read from register 0020 Hex of the
Inverter with a Slave address of 02.
D DSR Message
Byte No.
1
Slave address
2
Function code
3
Register No. of read start data
g
4
Number of registers of read data
5
6
CRC-16 check
7
8
7-12
g
g
g
Data
g
Data
:
Data
Chapter 7
MS B
LSB
MSB
LSB
MSB
LSB
:
Data
example
(Hex)
02
03
00
20
00
04
45
F0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents