Eaton 5125 User Manual page 57

Tower ups 1000–2200 va
Hide thumbs Also See for 5125:
Table of Contents

Advertisement

Table 6. Environmental and Safety
Operating Temperature
Storage Temperature
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Audible Noise
Surge Suppression
Safety Conformance
Agency Markings
EMC (Class A)
Table 7. Battery
UPS Configuration
EBM Configuration
Type
Charging
Monitoring
Eaton 5125 Tower UPS (1000–2200 VA) User's Guide
Low Voltage Models
Optimal battery performance: 25°C (77°F)
Up to 3,000 meters above sea level
Up to 15,000 meters above sea level
Less than 40 dBA Normal mode, typical load
ANSI C62.41 Category B, IEC 61000-4-5
UL 1778 4th Edition, UL 497A;
CSA C22.2, No. 107.3;
NOM-019-SCFI
cULus, cUL, NOM
FCC Part 15, ICES-003, VCCI
1000 VA: (2) 24V, 9 Ah internal batteries
1500 VA: (4) 48V, 7 Ah internal batteries
2200 VA: (4) 48V, 12 Ah internal batteries
PW5125 EBM-24: (8) 24V, 9 Ah batteries
PW5125 EBM-48: (8) 48V, 9 Ah batteries
Sealed, maintenance‐free, valve‐regulated, lead‐acid
Internal battery: approximately 3 hours to 90% usable capacity
at nominal line voltage after full load discharge
External battery: recharging at 80% load or less is recommended;
no more than 16x discharge time to 90% usable capacity at nominal line voltage after full
load discharge; an external battery charger is recommended for faster recharge times
Advanced monitoring for earlier failure detection and warning;
10°C to 40°C (50°F to 104°F)
0°C to 25°C (32°F to 77°F)
-25°C to 55°C (-13°F to 131°F)
5–95% noncondensing
Less than 55 dBA Battery mode
UL 1778 4th Edition, UL 497A (data line only);
IEC/EN 62040-1-1 and IEC/EN 60950
cULus and cUL; CE, C-Tick, LGA/GS, UL-GS
IEC/EN 62040-2, FCC Part 15, ICES-003
when using more than two EBMs.
auto detection of additional EBMs
S
05147304 Rev C www.eaton.com/powerquality
SPECIFICATIONS
High Voltage Models
CSA C22.2, No. 107.3;
51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents