SiUS092230EA
7.12 Compressor Sensor System Abnormality
H0
Error Code
Method of Error
The system checks the DC current before the compressor starts.
Detection
Error Decision
The voltage converted from the DC current before compressor start-up is out of the range 0.5 ~
Conditions
The DC voltage before compressor start-up is below 50 V.
Supposed
Broken or disconnected harness
Defective outdoor unit PCB
Causes
Troubleshooting
Part 6 Service Diagnosis
4.5 V.
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the (relay) harness for the
compressor.
Is the harness broken?
NO
Turn off the power. Then, turn on
the power to restart the system.
Restart
operation and error displayed
again?
YES
YES
NO
Troubleshooting for Outdoor Unit
Replace the harness.
Not a malfunction.
Keep observing.
Replace the outdoor unit
PCB (main PCB).
(R24613)
177