2.1
GENERAL (Figs. 2 and 3)
The installation of a Series E Gas Fired Steam Boiler should be carried out by competent personnel in
accordance with all relevant safety regulations. It is the responsibility of the installer to ensure that these
regulations are complied with.
The requirements and instructions contained in this Section generally relate to the boilers being installed
to operate on natural or manufactured gas. Where the boiler is to operate on L.P. Gas, special reference
should be made to Section 2.10 - Gas Supply, and Section 2.18 L.P. Gas Supply.
2.2

SITING

The boiler house should be sufficiently large to allow easy and safe access to all parts of the boiler for
operational and maintenance purposes. Reference should be made to Section 5 - General Data to
ascertain the relevant dimensions and special note taken of the required vertical clearance.
The flooring must be level, laid in a non-combustible material and be of sufficient strength to support the
boiler.
2.3

VENTILATION

Adequate fresh, clean air is necessary for safe and efficient combustion, and should be provided at high
and low level in accordance with BS 6644 1991.
Note:
(a)
Ensure there is adequate ventilation in the boiler room. Lack of ventilation will create a high
temperature and cause control lockout.
(b)
Do not keep exhaust fans running with windows, doors and vents closed, this will interfere
with the necessary boiler draught.
(c)
Do not store chemicals such as perclorethylene in the boiler house, the fumes may damage
the boiler and flue and cause the burner to lock out on flame failure.
SECTION 2
Boiler Model
6E
High Level (cm
2
)
305
2
Low Level (cm
)
610
8E
10E
15E
20E
360
420
560
700
720
835
1115 1395 1960 2520 3085 3645
GFSE-Std-0499

INSTALLATION

30E
40E
50E
60E
980
1260 1540 1820
2