Section 2 – Installation
General Specifications and Information about Fulton Pulse Combustion
1.
Commercial/Industrial Hydronic Boilers
Models
PHW300
BTU/HR. Input
300,000
Fuel
NG/LPG
Approx. Dry Weight
1,395 lbs.
Approx. Operating
1,680 lbs.
Weight
Floor Loading
235 lbs/ft
Power Required
120/60/1
Min. Required Gas
7"W.C.NG
Pressure
11" W.C. LPG
Max. Amp Draw
4.2
(FLA)
MAWP
60/160 PSI
Boiler Width
27.5 IN
Boiler Height
64 IN
Boiler Depth
37.8 IN

2. Introduction

a) The Fulton Pulse combustion hydronic boiler is an automatic gas fired, direct vent boiler.
This boiler utilizes pulse combustion principle. It requires no conventional burner controls,
no pilot and no chimney. The combustion components are of integral design with the heat
exchanger. For combustion, the boiler uses 100% outside air supplied through schedule
40 PVC pipe or can be vented conventionally. The products of combustion are vented
outdoors through non-corrosive venting materials which will withstand 480°F (249°C)
temperatures. These pipes can be routed either through a roof or through the side wall of
a building.
b) Each boiler is built to ASME and CSD-1 Codes, hydrostatically tested, test fired, and
shipped as a complete packaged unit. Gas, water, and electrical connections are similar
to conventional boilers.
c) All installations must be in accordance with the American National Standard "National
Fuel Gas Code," latest edition, and with the requirements of local utilities or other
authorities having jurisdiction. Such applicable requirements take precedence over the
general instructions herein.
PHW500
500,000
NG/LPG
1,395 lbs.
1,680 lbs.
2
2
235 lbs/ft
120/60/1
7"W.C.NG
11" W.C. LPG
4.2
60/160 PSI
27.5 IN
64 IN
37.8 IN
Fulton Heating Solutions, Inc. -- PHW Manual -- 2010-0713
Page 19
PHW750
PHW1000
750,000
1,000,000
NG/LPG
NG/LPG
2,275 lbs.
2,275 lbs.
2,625 lbs.
2,625 lbs.
2
2
270 lbs/ft
270 lbs/ft
120/60/1
120/60/1
7"W.C.NG
7"W.C.NG
11" W.C. LPG
11" W.C. LPG
4.2
4.2
60/160 PSI
60/160 PSI
27.5 IN
33.6 IN
76 IN
76 IN
50.8 IN
50.8 IN
PHW1400
PHW2000
2,000,000 NG
1,400,000
1,800,000 LPG
NG/LPG
NG/LPG
2,970 lbs.
3,785 lbs.
3,635 lbs.
4,385 lbs.
2
2
240 lbs/ft
250 lbs/ft
120/60/1
120/60/1
7"W.C.NG
7"W.C.NG
11" W.C. LPG
11" W.C. LPG
4.2
10.0
60/160 PSI
60/160 PSI
33.6 IN
33.6 IN
81 IN
81 IN
65 IN
75.8 IN

Hide quick links: