Monobloc Gas Valve - FULTON 60E Operator, Service & Parts Manual

E series gas fired steam boilers
Table of Contents

Advertisement

2
MONOBLOC GAS VALVES (FIG. 9)
ADJUSTMENTS 6E - 30E (MBDLE 407/412 B07)
(With in built pilot bypass valve)
Pilot gas rate should be set to a maximum of 10% of the full fire gas throughput.
ADJUSTMENTS
A
Main and Pilot Gas Governor.
B
Pilot gas range.
C
First and second stage -
initial lift adjuster, main gas valve.
D
Main gas throughput
E
Gas supply test point
F
Boiler side test point
ADJUSTMENTS 6E - 30E (MBDLE 407/412 BO1)
The Monoblock gas valve operates in two stages through two main shut-off valves:-
Stage 1.
maximum gas flow rate during the start gas proving period does not exceed 30% of the full
firing rate.
Stage 2.
NOTE: The time taken to open fully is set by the adjustment of the first and second stage initial lift adjuster.
F
ADJUSTMENTS
A
Main and Pilot Gas Governor.
B
First and second stage -
initial lift adjuster, main gas valve.
C
Main gas throughput
D
Gas supply test point
E
Boiler side test point
F
Low gas pressure switch
13
A
E
ACTION
Turn clockwise to increase gas pressure. Range 4 - 20 mbar.
Turn anticlockwise to increase and clockwise to decrease rate.
Slacken locking screw, turn fluted knob anticlockwise to
increase, clockwise to decrease.
The first valve opens fully and the second valve opens slowly such that the
The second valve is fully open.
A
D
ACTION
Turn clockwise to increase gas pressure. Range 4 - 20 mbar.
Slacken locking screw, turn fluted knob anticlockwise
to increase, clockwise to decrease.
GFSE-Std-0499
C
F
D
B
B
E
C
2

Hide quick links: