4.17 Restore Factory Calibration
Introduction
The factory calibration constants for all the input actuation types that can be
used with the controller are stored in its nonvolatile memory. Thus, you can
quickly restore the "Factory Calibration" for a given input actuation type by simply
changing the actuation type to another type and then changing it back to the
original type. Refer to Table 4-15 for procedure.
ATTENTION: A restored factory calibration overwrites any previous field
calibration done for the input and may change the High and Low Range Limits.
Be sure to protect any field calibration from accidental overwrites by configuring
the appropriate LOCKOUT selection after calibration.
See Section 4.15 for specific instructions to set the lockout.
Step
Operation
Set LOCKOUT to
1
NONE
2
Enter INPUT 1
Setup Group
Scroll through
3
Functions
4/00
Table 4-15 Restore Factory Calibration
Press
until you see:
SET UP
Upper Display = SET UP
Lower Display = TUNING
Until you see:
FUNCTION
Upper Display = one of the following:
NONE – all parameters are read/write
CAL – all parameters are read/write except Calibration
CONF – configuration parameters are Read Only; no writes
permitted
VIEW – Tuning and Setpoint Ramp parameters are
read/write. No other parameters can be viewed.
ALL – Tuning and Setpoint Ramp parameters are available
for read only. No other parameters can be viewed.
Lower Display = LOCK
[ ] [ ]
Until NONE is in the upper display
until you see:
SET UP
Upper Display = SET UP
Lower Display = INPUT 1 or 2
until you see:
FUNCTION
Upper Display = the current selection
Lower Display = INxTYP
to change the current selection to another selection
[ ] [ ]
until the lower display rolls through the rest of the functions and
FUNCTION
returns to:
Upper Display = the new selection
Lower Display = INxTYP
UDC2300 Universal Digital Controller User Manual
Operation
Result
57