3.6 Accutune Set Up Group

Introduction
Accutune II automatically calculates GAIN, RATE, and RESET TIME (PID)
tuning constants for your control loop. When initiated on demand, the Accutune
algorithm measures a process step response and automatically generates the
PID tuning constants needed for no overshoot on your process.
Fuzzy Overshoot Suppression, when enabled, will suppress or eliminate any
overshoot that may occur as a result of the existing tuning parameters, as the PV
approaches the setpoint.
Function Prompts

Table 3-5 ATUNE Group (Numeric Code 400) Function Prompts

Prompt
English
Numeric
Code
401
FUZZY
402
TUNE
403
AT ERR
4/00
Description
Selection or Range of Setting
Numeric
Code
Fuzzy
Overshoot
Suppression
Demand
Tuning
Accutune Error
Codes (Read
Only)
UDC2300 Universal Digital Controller User Manual
English
0
DIS
1
ENAB
DIS
0
TUNE
1
0
NONE
3
IDFL
4
ABRT
5
RUN
Configuration
Factory
Setting
DIS
TUNE
- - -
27