Timer Set Up Group; Table 3-2 Timer Group (Numeric Code 100) Function Prompts - Honeywell UDC 2300 User Manual

Universal digital controller
Hide thumbs Also See for UDC 2300:
Table of Contents

Advertisement

Configuration

3.3 Timer Set Up Group

Introduction
The Timer Set Up group allows you to configure a time-out period and to select
the timer start by either the keyboard (RUN/HOLD key) or Alarm 2. The optional
digital input can also be configured to start the timer. The timer display is
selectable as either "time remaining" (see TREM) or "elapsed time" (see ET).
Alarm 1 is activated at the end of the time-out period. When the timer is enabled,
it has exclusive control of the alarm 1 relay—any previous alarm 1 configuration
is ignored. At time-out, the timer is ready to be activated again by whatever
action has been configured.
Function Prompts

Table 3-2 TIMER Group (Numeric Code 100) Function Prompts

Prompt
English
Numeric
Code
TIMER
101
102
PERIOD
103
START
104
L DISP
105
RESET
106
INCRMT
22
Description
Selection or Range of Setting
Numeric
Code
Enable or
0
Disable Timer
1
Time-out Period
Timer Function
0
Start
1
Timer Display
0
1
Timer Reset
0
Control
1
Timer Count
0
Increment
1
UDC2300 Universal Digital Controller User Manual
English
DIS
ENAB
0:00 to 99:59
Select length of time in
Hours and Minutes, or
Minutes and Seconds.
KEY (Run/Hold key)
AL2 (Alarm 2)
TREM (time remaining)
ET (elapsed time)
KEY (Run/Hold key)
AL1 (Alarm 1 or Key)
MIN (Counts HR/MIN)
SEC (Counts MIN/SEC)
Factory
Setting
DIS
0:01
KEY
TREM
KEY
MIN
4/00