Configuration
3.10 Control Set Up Group
Introduction
The functions listed in this group deal with how the controller will control the
process including: Number of Tuning Parameter Sets, Setpoint Source, Tracking,
Power-up Recall, Setpoint Limits, Output Direction and Limits, Deadband, and
Hysteresis.
Function Prompts
Table 3-9 CONTRL Group (Numeric Code 800) Function Prompts
Prompt
English
Numeric
Code
PIDSET
801
SW VAL
802
803
LSP'S
804
RSPSRC
805
SP TRK
806
PWR UP
PWROUT
807
808
SP Hi
SP Lo
809
810
ACTION
32
Description
Number of Tuning
Parameter Sets
Automatic Switchover
Value
Local Setpoint Source
Remote Setpoint
Source
Setpoint Tracking
Power Up Controller
Mode Recall
TPSC (Three Position
Step Control) Output
Start-up Mode
Setpoint High Limit
Setpoint Low Limit
Control Output
Direction
UDC2300 Universal Digital Controller User Manual
Selection or Range of Setting
Numeric
Code
0
ONE
1
2KBD (Keyboard)
2
2 PR (PV switch)
3
2 SP (SP switch)
Value in engineering units
within PV or SP range limits
0
ONE
1
TWO
0
NONE
1
INP2
0
NONE
1
PROC (LSP tracks PV–
manual)
2
RSP (LSP tracks RSP–auto)
0
MAN (Manual/LSP/Failsafe)
1
ALSP (Auto/last LSP)
2
ARSP (Auto/last RSP)
3
AMSP (Last mode/last SP)
4
AMLS (Last mode/last LSP)
0
LAST (Last output)
1
FSAF (Failsafe output)
0 to 100 % of the PV range
0 to 100 % of the PV range
0
DIR
1
REV
Factory
Setting
English
Table continued next page
ONE
0.00
ONE
NONE
NONE
ALSP
LAST
2400
0
REV
4/00