Figure 2-8 Electromechanical Relay Output; Figure 2-9 Solid State Relay Output - Honeywell UDC 2300 User Manual

Universal digital controller
Hide thumbs Also See for UDC 2300:
Table of Contents

Advertisement

Load
Supply
Power
1 Control relays 1 and 2 are configured N.O. as shipped. Alarm relays
1 and 2 are configured N.C. as shipped. N.O. or N.C. configurations
are selectable by jumpers on the Main printed wiring boards.
See "Preliminary Checks" in this section of the
User Manual for details. Each SPST relay is rated at 5A, 120
Vac and 30 Vdc, 2.5 A 240 Vac. User-provided fuses should be sized
accordingly. For solid state relay outputs, see Figure 2-12.
See Figure 2-14 for Alarm and Duplex Output Connections.
See Table 2-2 and Table 2-3 for Control and Alarm Relay Contact information.
AC
Load
Power
Supply
1
If the load current is less than the minimum rated value of 20 mA,
there may be a residual voltage across both ends of the load even
if the relay is turned off. Use a dummy resistor as shown to
counteract this. The total current through the resistor and the load
current must exceed 20 mA.
2
Solid State relay is rated at 1 Amp at 25°C, linearly derated to 0.5
Amp at 55°C. Customer should size fuse accordingly.
See Figure 2-14 for Alarm and Duplex Output Connections.
See Table 2-2 and Table 2-3 for Control and Alarm Relay Contact
4/00
1
Control Relay #1
Load
5 amp Fast Blo

Figure 2-8 Electromechanical Relay Output

1 amp Fast Blo
2
Control Relay #1
Load
Dummy Resistor
information.

Figure 2-9 Solid State Relay Output

UDC2300 Universal Digital Controller User Manual
OUT1
OUT2/ALM2
5
9
4
10
24859
OUT1
OUT2/ALM2
5
9
4
10
1
24860
Installation
13

Hide quick links:

Advertisement

Table of Contents
loading