3.4

Technical Data

Type power
PROTECT C. 1000 (S)
PROTECT C. 2000 (S)
PROTECT C. 3000 (S)
UPS Input (single phase)
Rated input voltage
Voltage tolerance range
Nominal frequency
Frequency tolerance range
Current consumption at full load (max.)
PROTECT C. 1000 (S)
PROTECT C. 2000
PROTECT C. 2000 S
PROTECT C. 3000 (S)
Input power factor
Connection
Datalines
overvoltage protection
UPS Output (single phase)
Rated output voltage
Nominal frequency
Voltage waveform
1000 VA (cos ϕ = 0.7 lag.)
700 W
2000 VA (cos ϕ = 0.7 lag.)
1400 W
3000 VA (cos ϕ = 0.7 lag.)
2100 W
220 / 230 / 240 Vac
160 Vac – 300 Vac ± 5 Vac
Bypass 80 Vac – 264 Vac
50 Hz / 60 Hz
(automatic detection)
± 4 Hz
7 A
10 A
12 A
16 A
λ
0.96
Non-heating appliance
connector
RJ11 (phone, fax, modem)
RJ45 (Ethernet 10/100MBit/s)
220 / 230 / 240 Vac ±2 %
(configuration via software
"CompuWatch")
50 Hz / 60 Hz ± 0,2 %
(depending on mains)
Harmonic distortion
4 % THD (linear load)
7 % THD (non-linear load)