Fault Diagnosis / Fault Rectification; Error Messages - AEG PROTECT C. 1000 (S) Operating Instructions Manual

Table of Contents

Advertisement

6.2

Fault Diagnosis / Fault Rectification

The PROTECT C. generates detailed error messages.
Support personal can localise and interpret faults quickly and
precisely.
6.2.1

Error Messages

Problem
UPS does not start.
No indication, no audible
signal even though system
is connected to mains
power supply.
LED "Line" flashes and
audible signal sounding
every 3 minutes.
LED "Line" flashes and
LED "Battery" lights up.
LED "Line" and LED
"Bypass" light up even
though the power supply
is available. No supply of
connected loads.
LED "Inverter" and LED
"Battery" lights up, and
audible signal sounding
every 4 seconds.
LED "fault" lights, audible
signal once a second.
Cause
Mains and battery voltage
not in the tolerance range,
possible battery deep
discharge.
Phase and neutral
conductor at input of UPS
system are reversed.
Input power and/or
frequency are out of
tolerance.
Inverter not switched on.
Mains power supply has
failed. Automatic switch
to battery mode.
Overload of the UPS
system.
37
Solution
Check building wiring
socket outlet and input
cable.
Rotate mains power
socket by 180° or
connect UPS system.
Check input power
source (Voltage,
frequency) and inform
house electrician if
necessary.
Press On-Switch "ON"
for about 2 seconds.
Try to replace mains
supply (possibly
triggered fuse in sub
distribution). When
audible alarm sounding
every second, battery
is almost unloaded. At
this point it is time to
proceed with an system
shutdown of all you IT
equipment.
Reduce utilizations of
UPS by removing loads
of UPS output.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents