2.3 Technical data

UPS MODEL LIST
Protect C 6000(S) LCD
Protect C 10000(S) LCD
Protect C 6000BP LCD
Protect C 10000BP LCD
WEIGHT AND DIMENSIONS
Protect C 6000 LCD
Protect C 6000S LCD
Protect C 10000 LCD
Protect C 10000S LCD
Protect C 6000BP LCD
Protect C 10000BP LCD
ELECTRICAL INPUT
Selectable input Voltage range
Voltage at 100% Load
Nominal frequency
Frequency range
Bypass voltage range
Noise filtering
Input connection
Input cable
6000VA / 6000W
10000VA / 10000W
Battery pack for Protect C 6000 LCD
Battery pack for Protect C 10000
LCD
225x589x452 mm (WxHxD)
61kg
225x353x452 mm (WxHxD)
14kg
225x589x452 mm (WxHxD)
71kg
225x353x452 mm (WxHxD)
16kg
225x589x452 mm (WxHxD)
111kg
225x589x452 mm (WxHxD)
115kg
208/220/230/240V
176~276Vac
50/60Hz auto-sensing
40 Hz– 70 Hz,
for ≤60% rated load
45 Hz– 55 Hz (50Hz system)
54 Hz – 66 Hz (60Hz system)
for >60% rated load
176~264 Vac (default)
MOV for normal and common
mode noise
Hardwired
Not provided