Technical Data

Type rating
PROTECT 1.100
PROTECT 1.150
PROTECT 1.200
UPS input
Rated connection voltage
Voltage range without
battery operation
Frequency
Frequency tolerance range
Current consumption at full load (max.)
PROTECT 1.100
PROTECT 1.150
PROTECT 1.200
System disturbance factor
UPS output
Nominal voltage output
Nominal frequency
Type of voltage
Crest factor
10000 VA (cos ϕ = 0.7 ind.)
7000 W
15000 VA (cos ϕ = 0.7 ind.)
10500 W
20000 VA (cos ϕ = 0.7 ind.)
14000 W
3ph~ / N / PE
400 V/ 230 VAC
304 VAC – 478 VAC ± 3 %
(rectifier)
176 VAC – 261 VAC VAC ± 3 %
(bypass)
50 Hz / 60 Hz
(autom. detection)
± 4 Hz
13 A (3ph~) / 46 A (bypass)
19 A (3ph~) / 68 A (bypass)
25 A (3ph~) / 91 A (bypass)
λ ≥ 0.95
220 / 230 / 240 VAC ± 1%
(configuration via
"CompuWatch" software )
50 Hz / 60 Hz ± 0.1%
(dependent on mains frequency)
Sine, distortion
≤ 2% THD (linear load)
≤ 6% THD (non-linear load)
3:1
12