Control Circuit And External Battery Interface Connections 15/25/30 Kva; Recommended Wire Size And Torque Requirements - Toshiba 4200FA CT/XT User Manual

Toshiba 4200fa ct/xt uninterruptible power system three-phase 15/25/30/50 kva ups user's manual
Table of Contents

Advertisement

4.2 Control Circuit and External Battery Interface Connections 15/25/30 kvA

The following illustrates the wiring connections of the Control Circuits, and Battery Interface
Circuits.
(1) Low Battery
(
2) Battery Discharge
(3)
Fault
(4) Not Used
(5) Inverter Supply
(6) Inverter Supply
(7) P24A3
(8) Remote Run
(9) P24A3
(10) Remote Stop
(11) Bypass
(12) COMMON
(13) EPO
(14) EPO
4.2.1

Recommended Wire Size and Torque Requirements

UPS Control and Battery Interface 15/25/30 kVA
(TERMINAL #)
UPS CONTROL CIRCUITS
BATTERY CONTROL
CIRCUITS (3-6)*
*Indicates Class 1 wiring methods are to be used. Maximum Wire Size for Control Circuits is 12
AWG. Maximum for Battery is 2 AWG.
4200FA CT/XT User's Manual
TOSHIBA
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75 °C COPPER WIRING
TERMINAL
(1-24)*
BATTERY
(+/-)
Battery Connection
(+) Positive
(-)
Negative
15/25/30 kVA
TIGHTENING
AWG
TORQUE
14-16
8 in-lbs.
14-16
8 in-lbs.
4
51 in-lbs.
(3) Battery Shunt Trip
(4) Battery Shunt Trip
(5) Battery Aux.
(6) Battery Aux.
24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents