Control Circuit and External Battery Interface Connections 15/25/30/33 kVA

The following illustrates the wiring connections of the Control Circuits, and Battery Interface
Circuits.
(1) Low Battery
(2) Battery Discharge
(3) Fault
(4) Not Used
(5) Inverter Supply
(6) Inverter Supply
(7) P24A3
(8) Remote Run
(9) P24A3
(10) Remote Stop
(11) Bypass
(12) GND
(13) EPO
(14) EPO
4.2.1

Recommended Wire Size and Torque Requirements

UPS Control and Battery Interface 15/25/30/33kVA
TERMINAL
(TERMINAL #)
UPS CONTROL CIRCUITS
BATTERY CONTROL
CIRCUITS (3-6)*
*Indicates Class 1 wiring methods is to be used. Maximum Wire Size for Control Circuits is 12 AWG.
Maximum for Battery is 2 AWG.
TOSHIBA
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75° C COPPER WIRING
AWG
14-16
(1-24)*
14-16
BATTERY
(+/-)
Battery Connection
(+) Positive
(-) Negative
15/25/30/33 kVA
TIGHTENING
TORQUE
8 in-lbs.
8 in-lbs.
4
51 in-lbs.
23
(3) Battery Shunt Trip
(4) Battery Shunt Trip
(5) Battery Aux.
(6) Battery Aux.