Fire Alarm Type B; Fire Alarm Type A; Disable Zones, Alarm Points, Outputs, Etc; Disable Zone - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
13.12.1
13.12.2
13.13
13.13.1
If a fire alarm type A is received, the probability of a real fire is higher
than for a fire alarm type B. The alarm receiver can take different
actions depending on if it is a fire alarm type A or B.

Fire alarm type B

The output will be activated for fire alarm from one analog
addressable smoke, heat or multi
The output shall be programmed (via Win128) as type "Routing
equipment" and have the trigger condition "One detector alarm".

Fire alarm type A

The output will be activated for fire alarm from:
 Two or more analog addressable smoke, heat or multi
detectors.
 Any manual call point
 Any zone line input
 Any programmable input with the trigger condition "General
Fire"
The output shall be programmed (via Win128) as type "Routing
equipment" and have the trigger condition "Multiple detector
alarm".

Disable zones, alarm points, outputs, etc.

Temporary disablements are made via the menu H2 sub menus B1-B3
& B7-B9.
For more information see the EBL128 Operating
Instructions, chapter "Disable or re-enable (H2)".
Regular disablements are made via time channels, see chapter "Time
Channels", page 119.
Disabled alarm points and outputs are indicated by LED
"Disablements" and listed in menu H4/U1.
Fire alarm, pre-warning and fault signal can not be activated by a
disabled alarm point / zone.

Disable zone

A whole zone (all addressable alarm points within one zone, including
the manual call points) can be disabled via menu H2/B1. This menu is
also used to disable a conventional zone, i.e. a 3361 unit's zone line
input (Z) and expansion board 4580 zone line inputs.
Re-enable via menu H2/B4 or automatic re-enabling at a specified
time.
104
NOTE! A multi detector can have one presentation number (Zone-
Address) or two presentation numbers depending on how it is programmed
via Win128. One presentation number = one detector and two presentation
numbers = two detectors regarding fire alarm types A and B.
EBL128 Planning Instructions V1.1.x
104
detector only.