Parameters For Combined Decision Algorithm; National Holidays - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
16.3.3
16.4
In addition, a special password is required to change the fire alarm
parameters.

Parameters for combined decision algorithm

Offset, see "Parameters for smoke algorithms" above. Level, see
"Parameters for heat algorithms" above. See also "4300", page 34.
Offset, pre-warning: Offset value, default 50 (5.0%/m).
Offset, alarm: Offset value, default 58 (5.8%/m).
Level, pre-warning: Level, default 50 (°C)
Level, alarm: Level, default 58 (°C).
NOTE! Changing these parameters will affect the sensitivity and
detection time and should be done by authorised personnel only!!!!!
In addition, a special password is required to change the fire alarm
parameters.

National Holidays

Figure 29. The Win128 tab page "Control Unit Properties" with
the tab "National Holidays" open.
Up to twenty national holidays can be downloaded to EBL128.
Each national holiday can be added one by one, i.e. by selecting a date
in the drop-down list (up to the right) and click "Add" to add a row
with the date to the list (to the left).
121
EBL128 Planning Instructions V1.1.x