Address Setting Check - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
15.9
4352: This detector has no self diagnosis of internal devices.
4350: This detector has self diagnosis of internal devices (but no
separate fault output).
4301: This detector has self diagnosis of internal devices.
4300: This detector has self diagnosis of internal devices.

Address setting check

The indication LED in the detectors 4301 and 4300 (in all modes) will
blink every second when the detector is powered up and if the detector
address is not set with the Address setting tool 3314, i.e. as long as the
address is "000". Normally the address should be set in the interval
001-127.
115
EBL128 Planning Instructions V1.1.x