Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
13.20.2
13.21
13.21.1
Shows the already programmed texts for each alarm point / zone.
These texts will be displayed in the control unit and all "display units"
1826, 1828, 1735, 1736 and 1728 if there are no other texts
programmed.
Text column
The text to be shown in this "display unit" for the alarm point / zone
respectively, has to be typed (edited) here. NOTE! In this "display
unit" the text in the "Text" column will now be shown instead of the
text in the "Text in control unit" column, for the alarm point / zone
respectively.
Downloading texts to the EPU 1728, AAUs 1735 / 1736
and ext. FBPs 1826 / 1828
The "display units" have to be connected to EBL128 and the address
114
and mode
have to be set in the "display units".
The texts will then be downloaded at the same time as the EBL128
site specific data (SSD) is downloaded via Win128.
The texts can as an alternative be downloaded in one "display unit" at
a time but the PC (with Win128) has nevertheless to be connected to
EBL128.

Real time clock (RTC)

EBL128 has a built-in RTC that is used for date and time presentation
in conjunction with fire alarms, faults, log events, etc. It also controls
the time channels 2-4. The RTC has no backup battery, i.e. the date,
time, etc. has to be set (via menu H3) after loss of the power supply
(no mains and no battery backup).

Daylight saving time

The time is automatically changed when the Daylight saving time
period starts and stops respectively. This is depending on which
convention that is used.
 Australian convention: Forward 1 hour the first Sunday in
October, 02:00  03:00. Backward 1 hour the first Sunday in
April, 03:00  02:00.
 New Zealand convention: Forward 1 hour the last Sunday in
September, 02:00  03:00. Backward 1 hour the first Sunday
in April, 03:00  02:00.
 All other conventions: Forward 1 hour the last Sunday in
March, 02:00  03:00. Backward 1 hour the last Sunday in
October, 03:00  02:00.
114
S/W mode xxxx – 1587. (xxxx = e.g. 1826/28)
115
In the "Download SSD to Control Unit" dialog box the "Download to
FBP / AAU / EPU" check box has to be selected. (As an alternative the
"Modified FBP / AAU / EPU only" check box can be selected.)
102
EBL128 Planning Instructions V1.1.x