Peripheral devices

Alarm points are connected to the COM loop.
Wireless smoke detectors are "connected" to a Base station, which is
connected to the COM loop.
Short circuit isolators are connected to the COM loop.
30
I/O Matrix boards
are plugged ("piggy back") to an Application
board (Fan, Generic or Zone), which is connected to the COM loop.
Sounders, door release magnets, etc. are connected to the
programmable outputs in EBL128 (S0-S1 and/or R0) and/or to output
units connected on the COM loop. Addressable sounders (alarm
devices) are connected directly on the COM loop.
Input devices as key cabinet, timer, external fault, etc. are connected
to programmable inputs, i.e. to input (I0) in EBL128 and/or to input
units connected to the COM loop.
31
Display units
are connected to the RS485 interface in EBL128.
Alternatively, German Fire Brigade Control Panels (Feuerwehr-
3
Bedienfeld) FBF 2003
(Feuerwehr-Anzeigetableau) FAT 2002
interface in EBL128.
Routing equipment (Fire brigade tx / Fault tx) is normally connected
to the R0-R1 outputs in EBL128. Regarding the Fire brigade tx, see
chapter "Fire alarm type A and Fire alarm type B", page 96.
German routing equipment, key cabinet and extinguishing system are
connected to programmable inputs / outputs in EBL128 and
Expansion board 4583.
For more information, see the following chapters and/or the Product
Leaflets on our web site:

COM loop units

The COM loop can handle up to 127 addressable COM loop units.
NOTE!
Depending on the type of units and the number of units the total
current consumption will vary. This and the cable resistance will
affect the cable length.
See also chapter "Current consumption", page 134 and drawing 128-
11.
29
Directly (addressable) or via an input unit 3361. The programmable input
I0 in EBL128 can be used as a fire alarm input (NO/NC).
30
The I/O Matrix board 4582 is described in chapter "Expansion boards
458x", page 22.
31
External Presentation unit 1728, External Fire Brigade Panel 1826 / 1828
and Alert Annunciation unit 1735 / 1736
32
Conventional detectors can be connected to an 8 zones expansion board
4580 or to the zone line input (Z) on each addressable I/O unit 3361.
EBL128 Planning Instructions V1.1.x
29
and/or German Fire Brigade Indicator Panels
3
are connected to the RS485