Control Unit Properties (Settings); Control Unit Properties; Aaf Times; Alert Annunciation Times - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
16
16.1
16.1.1
16.1.2

Control unit properties (settings)

Figure 24. The Win128 tab page "Control Unit Properties" with
the tab "Control Unit Properties" open.
NOTE! The default settings in the different tabs / dialog boxes might
vary depending on the convention.

Control Unit Properties

Name: Normally not changed (but can be changed when necessary).
The following is read only information that will be automatically
updated when the SSD is edited.
LCD bottom row
The LCD in EBL128, can in quiescent state, on the bottom (second)
row show a 40 characters user definable text.

AAF times

Acknowledge periode: 30 sec.
30 is default. 10--60 seconds (= 1 min.) are possible to set.
Investigation periode: 3 min.
3 is default. 0-3 minutes are possible to set.

Alert annunciation times

See also chapter "Alert Annunciation", page 92.
Acknowledgement time: 30 sec.
30 is default. 5, 10, 15, - -60 seconds (= 1 min.) is possible to set.
126
Default is an empty string (i.e. no text) except in the Swedish convention
where the text is "
116
EBL128 Planning Instructions V1.1.x
126
Normal drift
"

Advertisement

Table of Contents
loading

Table of Contents