Zone line input alarm delay time

Not valid in the Australian and New Zealand convention respectively.
One of the following alternatives can be selected. It is then valid only
for the zone line inputs with the option "Delayed " selected in its
Win128 dialog box.
NOTE! This delay starts when the alarm normally should have been
activated.
 30 seconds (default)
 60 seconds
See also chapter "Delayed alarm", page 92.

Miscellaneous

Use special menu during fire alarms: This special menu (X1-
X9) can be used during fire alarm to see all the fire alarms but
first of all it can be used to display faults and disablements in the
system. Alarm points, zones, control outputs and alarm devices
can also be disabled / re-enabled via this menu. . If this menu is
not selected, it is a violation to the EN54-2 standard. See also
EBL128 Operating instructions, chapter "Fire alarm menu X1-
X9".
Door open in CU will disable routing equipment: If the "Fire
brigade tx" and "Fault tx" outputs in EBL128 shall be disabled
when the door is opened, this checkbox shall be marked.
Disabled routing equipment is a violation to the EN54-2
standard.
Door open in EBL128 or in an ext. FBP is indicated by LED
"Door open" in the C.U.
Disabled outputs for routing equipment are indicated by the
LED "Disablements" (L8) and "Fault / Disablements Fire
brigade tx" (L15) and listed in menu H4/U1.
In the display is shown:
Fire alarm routing disabled
(by open door in CU)
Flash LED on MCP 3333, 3339: If the manual call point's
built-in LED shall flash each time EBL128 communicates with
the call point, this checkbox shall be marked. If this checkbox is
unmarked, the LED will not be turned on until the call point is
operated.
Silence buzzer by door switch: If the buzzer in the c.i.e. shall
be silenced when the door is opened this checkbox shall be
marked, but this is a violation to the EN54-2 standard.
Fault latching: Faults incl. corrected faults always have to be
acknowledged when this option is selected (default).
selected, corrected faults will be automatically acknowledged.