Operating The Ups; Initial Startup (First Power-Up) - Toshiba 1600XP SERIES Installation And Operation Manual

1600xp series single phase - 3.6/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

11. Operating the UPS

The 1600XP should be installed by a certified electrician. Once installed, the 1600XP is designed to be
operated by any user. Anyone not familiar with this UPS should read the manual before attempting to
operate it.

11.1 Initial Startup (First Power-Up)

The first time the UPS is activated after being shipped from the factory, these parameters need to be
set by the customer for site specific ratings. Input Rated Voltage, Output Rated Voltage, UPS Date, and
UPS Time.
The input frequency defaults to 60 Hz.
The first screen displayed during the initial startup sequence requires the operator to select the nominal
Input Voltage. Select from 208V, 230V, or 240V, and press the Write key.
If the command has been accepted, the word "Successful" will appear at the bottom left side of the
display.
1.
Repeat the process in step 1 in selecting the Rated Output Voltage.
2.
Use the keypad to type in the current date in the format: Mon 10/05/2009 and press Write.
3.
Use the keypad to type in the current time in 12 hour format: 12:15 PM and press Write.
4.
The Main screen is now displayed. Verify the UPS is in BYPASS mode. The mode (lower right side
of the display) should display Bypass. If it does not display Bypass, press and momentarily hold
the STOP button on the Main display.
5.
With the UPS in bypass mode, cycle power to the UPS as follows:
At the rear of the UPS switch the main circuit breaker MCCB to OFF.
Leave the UPS off until the DC bus is safely discharged (approximately 5-10 minutes).
Restart the UPS by switching the main circuit breaker ON.
The table below summarizes the initialization parameters:
ID
Command
111
Rated Vin
215
Rated Vout
634
UPS Date
635
UPS Time
20
Select from 208V, 230V, or 240V, and press Write.
Select from 208V, 230V, or 240V, and press Write.
Input the date in this format: Mon 10/05/2009 and press Write.
Input the current time in 12 hour format: 12:15 PM and press Write.